FLUID CIRCULATION
The forced circulation of the fluid in the coil is produced by the circulation pump centrifugal horizontal axis, with a single impeller. The pump ensures a constant and uniform circulation of the fluid at design speed that allows to haven’t oil overheating with consequent possibility of cracking, and then the formation of carbonaceous deposits.
Was made the complete shielding of the combustion chamber and of the links the front and rear of the coil between the surfaces exposed to radiation and convection at the surface to ensure proper and effective heat flux.
CONSTRUCTION
The shell plating welded to the nervate heads, that support the doors closed, contains the coil, free to expand without distorting the containment structure. The flue pipe rests on the cylindrical shell and can support a chimney flue.
DOOR CLOSING
In sheet quality, high temperature resistant mineral fiber insulation and refractory material.
The heat insulation material is concentrated in the central area on the side of the burner and center rear on the inversion of the flame, resulting in very low thermal inertia. In the case of accidental outage of circulation pump, heat transfer caused by thermal inertia is minimized.
OUTPUT/INPUT OIL
The output and input thermal oil are made with flanged PN16 connected to internal distribution oil collector to the coil.
Is supplied loose the flange connection between the pump and the flange of the return to the boiler.
INSULATION
It is made by coating the boiler body with mineral wool mattresses high density (100 kg/m3.) and minimum total thickness of 100 mm.
The outer coating is made of stainless steel sheet.
MAINTENANCE
Access to the coils is perfectly possible to open doors for easy cleaning of the three passes of fumes.